Cisco 6509机箱背部红灯分析报告


1 6509 主引擎 SYSTEM亮红灯2 6509 机箱背面线路集成板亮红灯二、设备硬件指示灯层面分析:
思科官方针对主引擎上,system亮灯的几种情况的说明:Green—All chassis environmental monitors are reporting OK.Orange—The power supply has failed or the power supply fan hasfailed.Red—Incompatible power supplies are installed.(电源异常)The redundant clock has failed.(冗余时钟异常)One VTT1 module has failed or the VTT module temperature minorthreshold has been exceeded2 .(一块VTT模块异常,或者VTT模块温度异常)Two VTT modules fail or the VTT module temperature major thresholdhas been exceeded3.(两块VTT模块异常,或者温度异常)The temperature of the supervisor engine major threshold has beenexceeded(引擎温度异常)
三、设备系统告警层面分析:免费云主机域名
6509有如下告警:environmental alarms:system minor alarm on operating VTT count(raised 18w1d ago)system minor alarm on VTT 2 OK (raised18w1d ago)四、设备系统层面分析:
查看6509硬件状态,有如下状态描述:VTT 2: VTT 2 OK: not OK VTT 2 outlettemperature: 29C说明VTT2 模块系统检测状态不正常VTT:电压终端模块,用于Catalyst交换总线。如果没有安装冗余Supervisor引擎,并且VTT模块处于轻微或者严重温度过高状态,则系统就会关机。在背板上有三个电压调节器(VTT)。如果一个VTT模块出现故障,则就会出现轻微告警。如果两个出现故障,则就会出现重大告警,正确措施就是关闭系统
五、结论:
6509机箱背板中,VTT2 电压终端模块出现异常,现在系统中仍有2VTT模块正常工作,如果再出现一块VTT电压终端模块异常,将会使系统严重告警,如果情况严重可能导致整台6509停止工作。一台6509最大只能承受2VTT模块异常。